SPMO

Nominal voltage (Un)

3×230/400 V

Intended fot the network system

TN, TN-S, TT, IT

Rated insulation voltage (Ui)

690 V

Rated impact voltage (Uimp)

6kV

Rated current (InA)

630 A

Rated output current (InC)

2 and 3 outputs

4 outputs

>4 outputs

RDF = 0.9

RDF = 0.8

RDF = 0.7

560 A

500 A

440 A

Short-circuit current (Icw)

20 kA / 1 s

Usage class

AC23

Electromagnetic compatibility (EMC)

Class index B

Mechanical protection grade

IP44, IK10

Weight (without meter)

25 kg – 40 kg

Thermal stability

70°C, 168h

Fire resistance

960°C ± 15°C

Low temperature resistance

-30°C

Flammability index

V0

Applied standards, laws and documentation

HRN EN 61439-1, HRN EN 61439-2,HRN EN 61439-5, HRN EN 62208

Certificat No. LVD 30140029 – Končar Institut

Certificat No. DN226/2013 – IEL Institut Warszawa

Test report No. 8381/NZL/NBR/13 – IEL Institut Warszawa

Pošaljite nam poruku